EKL17-40 6kA B Type RCBO
Inquire
Standard | IEC/EN61009-1 |
Protection | Ground fault, Overcurrent and short circuit, Over-voltage(selectable) |
Type of trip | Ground fault : Electronic |
Overload and short circuit :Thermo-magnetic | |
Type of protection (electric leakage) | AC,A |
No.of poles | 1P+N 2module , N line with disconnected |
Rated currents (In) | 6,10,16,20,25,32,40A,63A,80A |
Rated sensitivity currents I△n | 30,100,300mA |
Residual current off-time under I△n | ≤ 0.1s |
Rated residual making and breaking capacity(I△m) | 500A(In≤50A), 10In(In>50A) |
Rated voltage (Ue) | 230/240V~ |
Rated frequency | 50/60Hz |
Rated breaking capacity | 6,000A |
Energy Limiting Class | 3 |
Rated impulse withstand voltage (1.2/50) Uimp | 4,000V |
Dielectric test voltage at Ind. Freq.for 1 min | 2kV |
Thermal release characteristic | (1.13-1.45) x In |
Magnetic release characteristic | B:(3-5) x In, C:(5-10) x In |
Electrical life | 4,000 Cycles |
Mechanical life | 10,000 Cycles |
Contact position indicator | Yes |
Ground fault indicator | Yes |
Protection degree | IP20 |
Ambient temperature | -25℃ to +40℃, Max.95% humidity |
Terminal connection type | Cable/Pin-type busbar/Fork-type busbar |
Max. terminal size for cable | 25mm2 |
Max. tightening torque | 2.5N.m |
Installation | Mounting on 35mm DIN rail |
Connection | From top |