Standard |
IEC/EN60898-1 |
IEC/EN60947-2 |
Protection |
Overcurrent and short circuit |
Type of trip |
Thermo-magnetic |
No.of poles |
1P,1P+N,2P,3P,3P+N,4P |
Rated currents (In) |
1,2,3,4,5,6,10,16,20,25,32,40,50,63A |
Rated voltage (Ue) |
240/415V~ |
Rated frequency |
50/60Hz |
Rated breaking capacity |
6,000A |
Energy Limiting Class |
3 |
Rated impulse withstand voltage (1.2/50) Uimp |
6,000V |
Dielectric test voltage at Ind. Freq.for 1 min |
2kV |
Thermal release characteristic |
(1.13-1.45) x In |
(1.05-1.30) x In |
Magnetic release characteristic |
B:(3-5) x In, C:(5-10) x In |
(8-12) x In |
Electrical life |
8,000 Cycles |
Mechanical life |
20,000 Cycles |
Contact position indicator |
Yes |
Protection degree |
IP20 |
Ambient temperature |
-5℃ to +40℃, Max.95% humidity |
Terminal connection type |
Cable/Pin-type busbar |
Max. terminal size for cable |
25mm2 |
Max. tightening torque |
2.5N.m |
Installation |
Mounting on 35mm DIN rail |
Connection |
From top and bottom |