Innovative Compact RCBO Protector Dedicated to Charging Piles, with a Width of 18mm —— The Perfect Combination of Safety and Space Utilization

Publish Time: Author: ETEK Electric Visit: 22

Basis

RCDs protecting each connecting point in accordance with 722.411.3.3 shall comply at least with the requirements of an RCD type A and shall have a rated residual operating current not exceeding 30 mA.

Where the EV charging station is equipped with a socket-outlet or vehicle connector complying with IEC 62196 (all parts), protective measures against DC fault current shall be taken, except where provided by the EV charging station. The appropriate measures, for each connection point, shall be as follows:

  •  the use of an RCD type B; or 
  • the use of an RCD type A in conjunction with a residual direct current detecting device (RDC-DD) complying with IEC 62955; or 
  • the use of an RCD type F in conjunction with a residual direct current detecting device (RDC-DD) complying with IEC 62955.

RCDs shall comply with one of the following standards: IEC 61008-1, IEC 61009-1, IEC 60947-2 or IEC 62423.

 


Product Model: EKL19-40B

Technical Parameters:

Ue: 230 /240V~ (1P+N)

Frequency: 50/60Hz

In: 6A, 8A, 10A, 13A, 16A, 20A, 25A, 32A, 40A Instantaneous Tripping Type: B- & C- type

I∆n: 30mA

Residual Current Type: type -B
Im=3000A
Icn= Ics= 6000A
Energy limiting class 3,
Ambient temperature -25°C to +55°C. 

Product Features

  1. Ultra-thin Design, Saving Space
    With a width of only 18mm, it is more compact than traditional RCBOs, optimizing the space in the distribution box. It is especially suitable for the compact installation requirements of charging piles.
  2. Multiple Protections, Safe and Reliable
    Short-circuit Protection: Quickly cuts off the faulty current to prevent damage to the equipment.
    Overload Protection: Automatically monitors the current to avoid overloading of the circuit.
    Leakage Protection: Supports leakage detection of Type A (alternating current + pulsating direct current) and Type B (full direct current), meeting the requirements of different charging piles.
  3. Disconnectable N Pole, Higher Safety
    The design of a disconnectable N pole is adopted to ensure that the charging pile is completely powered off in case of a fault, avoiding potential risks and complying with the latest safety standards.
  4. High Compatibility, Widely Applicable
    It is suitable for household, commercial and public charging piles, is compatible with various charging devices, and provides stable and reliable protection.

Application Scenarios

✅ Home Charging Piles —— Ensuring the Safety of Home Charging

✅ Commercial Charging Stations —— Meeting High-load Requirements

✅ Public Charging Facilities —— Ensuring Long-term Stable Operation Why Choose Our RCBO?

 

 

Why choose our RCBO?

✔ Space-saving - 18mm ultra-thin design, optimizing the power distribution layout

✔ Multiple protections - Comprehensive protection against short circuits, overloads, and electric leakage

✔ High adaptability - Type A/Type B options available to meet the needs of different charging piles

✔ Safety upgrade - N pole can be disconnected to eliminate potential safety hazards

✔ Product certifications - Complete certifications from various countries

 

More detial check

Conclusion

Our RCBO protector dedicated to charging piles, with a width of 18mm, takes compact design, multiple protections and high safety as its core, providing a smarter and more reliable electrical protection solution for electric vehicle charging facilities.

It safeguards the safety of your charging piles!